Humidistats
Relative humidity (RH) in buildings is recommended to be maintained between 25% and 80% in winter and 20% and 70% in summer. Regin humidity transmitters keep it under control at any season. Regin humidistat are used for controlling humidifying and/or dehumidifying in HVAC systems. The humidistats have hair or a synthetic element as sensor medium. The sensor stretches as the humidity increases and shrinks as the humidity decreases. The changes are transmitted to a micro switch. The setpoint can be set at between 10 and 100% RH.
HR-S - electro-mechanical room humidistat with a synthetic element.
HR1, HR1-DH,HR2 - electro-mechanical room humidistat with change-over contact. The humidistat is intended for wall-mounting and has tamper proof settings.
HMH - electro-mechanical humidistat with change-over contact. The humidistat is intended for wall-mounting or for mounting in ducts.
HD - electronic humidistat with one or two relay outputs. The humidistat is intended for mounting on DIN-rail. An external transmitter is connected to the module.
HRD1-24 - electronic humidistat with one relay output. For wall-mounting .
HDD1-24 - electronic humidistat with one relay output. For duct-mounting . ---------------------------------------------------------------------------------- ELECTRO-MECHANICAL 1-STEP HUMIDISTAT HR-S
|
Humidistat HR-S Output: 1, 230 V AC, 5A, change-over Setpoint: 35...95% RH Hysteresis: 7% RH Mounting: Wall-mounting Protection class: IP30 |
 | ---------------------------------------------------------------------------------- ELECTRO-MECHANICAL HUMIDISTAT HR
|
Humidistat HR Output: 5A, 250 V AC, (HR1/HR2) Output: 10A (HR1-DH) Setpoint: 10...95% RH Hysteresis: 4% RH Step differential: (HR2) 0...30 % RH Mounting: Wall-mounting Protection class: IP21
HR1 - 1-step, 5A HR1-DH - 1-step for dehumidifying, 250 V AC HR2 - 2-step, 5A |
 | ---------------------------------------------------------------------------------- ELECTRO-MECHANICAL HUMIDISTAT HMH
|
Humidistat HMH Output: 10 A, 250 V AC, change-over Setpoint: 10...100% RH Hysteresis: 3% RH Step differential: (HMH2) 0...25 % RH Mounting: Duct or wall-mounting Protection class: IP54
HMH - 1-step HMH2- 2-step HPH148 - proportional 0-148 ohms HPH1000 - proportional 0-1000 ohms |
 | ---------------------------------------------------------------------------------- ELECTRONIC HUMIDISTAT HD
|
Humidistat HD Supply voltage: 24 V AC +/-10%, 2 VA Output: 1 arba 2, 10 A, 250 V AC Input: 0...10 V DC Humidity rangeability: 20...95% RH Hysteresis: 1...20% RH Step differential: (HD2) 0...20 % RH Mounting: DIN-rail, 3 modules Protection class: IP20
HD1-24/D - 1-step, change-over contact HD2-24/D- 2-step, closing contacts |
 | ---------------------------------------------------------------------------------- ELECTRONIC 1-STEP HUMIDISTAT HRD1-24
|
Humidistat HRD1-24 Supply voltage: 24 V AC/DC +/-15%, 1 VA Output: 1, 5A, 24 V AC, change-over Setpoint: 10...95% RH Hysteresis: 3...15% RH Mounting: Wall-mounting Protection class: IP65 |
 | ---------------------------------------------------------------------------------- ELECTRONIC 1-STEP HUMIDISTAT HDD1-24
|
Humidistat HDD1-24 Supply voltage: 24 V AC/DC +/-15%, 1 VA Output: 1, 5A, 24 V AC, change-over Setpoint: 10...95% RH Hysteresis: 3...15% RH Insertion length: 60...230, adjustable Mounting: Dust-mounting Protection class: IP65 |
 | ---------------------------------------------------------------------------------- Ever Yours NIT
|