Flanged valves and actuators
Flanged valves GTVS, GTRS are for hot and cold water systems. the valves can be changed from 2-way to 3-way and vice-versa without dismantling. The OVA-F1/F2 adapter for Regin actuators is factory mounted.
The NTVS-series is intended to control hot and cold water, glycol mixed water, steam and district heating within the temperature range -5...+185 ° C. The valve is pressure-balanced and is therefore able to handle high differential pressures with low force. This means that an actuator with low force can be used. The valve has softseal of carbon-filled teflon between cone and seat, which makes it completely tight. It has a self-adjusting packing box in teflon and an O-ring in Viton. NTVS valves meet the requirements of DIN-standard DIN3202/F1 and ISO 5752 table 1.
2SAS and 2SBS flanged valves are for heating, district heating and air handling systems.
Flanged valves FRS are for heating, district heating and air handling systems. FRS-valves are intended for use together with Regin RVA actuator. Adapters are also available for other actuator brands. The valves are mainly intended for district heating and were primarily developved to replace the TAC valve type STL. The valve is pressure-balansed and is therefore able to handle high differential pressures with low force. This means than an actuator with low force can be used.
Flanged valves FRSD are for heating, district heating and air handling systems. The FRSD-valves meets the requirements of DIN-standard DIN 3205/F1 and ISO 5752 table 1. FRSD-valves are intended for use together with Regin RVA actuators. Adapters are also available for other actuator brands. The valves are mainly intended for district heating and were primarily developved to replace the TAC valve type STL. The valve is pressure-balansed and is therefore able to handle high differential pressures with low force. This means than an actuator with low force can be used.
RVAR5 is a series of valve actuators intended only for Regin's MMV and MMR valves.
The valves V538C3... are intended for use in heating and ventilation systems together with Honeywell actuators.
Flanged valves V538C6... intended for continuous control of cold/hot water and steam together with Honeywell actuators.
The valves V176... are intended for cold and hot water within a temperature range of -5 to + 185° C together with Honeywell actuators. --------------------------------------------------------------------------------- FLANGED VALVES GTVS/GTRS
--------------------------------------------------------------------------------- FLANGED VALVES NTVS (DIN standard)
|
Flanged valves NTVS Flow characteristics: Equal percentage Max diff. pressure: 1,6 Mpa Fluid temperature: -5...+185° C Max leakage: 0,00% of Kvs Rangeability: 100:1 Pressure rating: PN16
More > NTVS.pdf |
 | --------------------------------------------------------------------------------- DISTRICT HEATING VALVES 2SAS/2SBS
|
District heating valves 2SAS/2SBS Flow characteristics: Equal percentage Max diff. pressure: 1,6 Mpa Stroke: 20 mm (B2SB100-160 =38 mm) Fluid temperature: -5...+185° C Rangeability: 50:1 Max leakage: 0,1% of Kvs Pressure rating: PN16
More > 2SAS-2SBS.pdf |
 | --------------------------------------------------------------------------------- DISTRICT HEATING VALVES FRS
|
District heating valves FRS Flow characteristics: Equal percentage Max diff. pressure: 1,6 Mpa Stroke: 20 mm Fluid temperature: -5...+150° C Rangeability: 100:1 Max leakage: 0,00% of Kvs (PTFE-sealing) Pressure rating: PN16
More > FRS.pdf |
 | --------------------------------------------------------------------------------- DISTRICT HEATING VALVES FRSD
|
District heating valves FRSD Flow characteristics: Equal percentage Max diff. pressure: 1,6 Mpa Stroke: 20 mm Fluid temperature: -5...+150° C Rangeability: 100:1 Max leakage: 0,00% of Kvs (PTFE-sealing) Pressure rating: PN16
More > FRSD.pdf |
 | ---------------------------------------------------------------------------------- VALVE ACTUATOR RVAR5
|
Valve actuator Supply voltage: 24 V AC Control signal: 3-point, 0...10 V or 2...10 V DC Power consumption: Max 4,5 VA Stroke: 20 mm fixed, 10...30 mm, self stroke adjustment (for analogue output only) Stroke time: 3 s/mm Protection class: IP54
More > RVAR.pdf |
 | --------------------------------------------------------------------------------- VALVE FOR HOHEYWELL ACTUATORS V538C3...
|
Valve V538C3...
Valve flow type: Square Fluid temperature: -5...+150° C Rangeability: 50:1 Stroke: 20 mm Pressure rating: PN16
More > V538C.pdf |
 | --------------------------------------------------------------------------------- VALVE FOR HOHEYWELL ACTUATORS V538C6...
|
Valve V538C6... Valve flow type: Square Fluid temperature: -5...+120° C Max leakage: 0,1% of Kvs Rangeability: 50:1 Pressure rating: PN16
More > V538C.pdf |
 | --------------------------------------------------------------------------------- DISTRING HEATING VALVE FOR HOHEYWELL ACTUATORS V176...
|
District heating valves V176... Valve flow type: Square Max diff. pressure: 1,6 Mpa Stroke: 20 mm (V176B5457 = 38 mm) Fluid temperature: -5...+185° C Rangeability: 50:1 Max leakage: 0,1% of Kvs Pressure rating: PN16
More > V176A.pdf |