CO2 transmitters
The Regin CO2-transmitters give direct information about the concentration of CO2 in the room or building. Based on these values the ventilation system is constantly controlled to provide an optimum concentration of co2 in the air.
• Very high accuracy due to patented auto-calibration function with infrared light measuring and reference measuring system • Low risk for contamination • Short response time • High long-term stability • Long calibration interval - more than 5 years and no calibration necessary at installation
The new CO2RT series with the patented auto calibration process, sets new standards in CO2 measuring for HVAC applications. In the same casing the CO2RT-series combines measuring of CO2-level, temperature and optional relative humidity. There are different models, with or without display and relay.
CO2DT measures the concentration of carbon dioxide in ducts. the calibration interval is more than 5 years and no calibration is necessary at installation. ---------------------------------------------------------------------------------- CARBON DIOXIDE (CO2) TRANSMITTER CO2RT
|
Transmitter CO2RT Supply voltage: 24 V AC +/-15%, 50...60 Hz or 15...35 V DC, 3 VA Working range: 0...2000 ppm Working range Temperature: 0...50 °C Working range Humidity:10...90% RH Accuracy CO2: <+/-(50 ppm + 2% of working range) Accuracy Temperature:+/-0,3°C Accuracy Humidity: +/- 3% (30...70% RA) +/- 5% (10...90% RH) Relay contact data: Max 1 A at 50 V AC, Min 1mA at 5 V DC Mounting: Wall-mounting Protection class: IP54
CO2RT - transmitter and temperature CO2RT-D - transmitter and temperature, with display CO2HRT - transmitter, temperature, humidity CO2HRT-D - transmitter, temperature, humidity, with display CO2RT-R - transmitter with relay CO2RT-R-D - transmitter with relay and display |
 | ---------------------------------------------------------------------------------- CARBON DIOXIDE (CO2) TRANSMITTER CO2DT
|
Transmitter CO2DT Supply voltage: 24 V AC +/-20%, 50...60 Hz or 15...35 V DC, 3 VA Working range: 0...2000 ppm Output: 0...10 V DC Accuracy: +/-(50 ppm + 2% of measured value) Relay contact data: Max 1 A at 50 V AC, Min 1mA at 5 V DC Mounting: Duct-mounting Protection class: IP54
CO2DT - transmitter, 0...2000 ppm CO2DT-R - transmitter with relay, 0...2000 ppm |
 | ---------------------------------------------------------------------------------- Ever Yours NIT
|